How plants respond, and how to find the model
Every controller rests on a model of how the plant responds. Twelve interactive plants show where time constants, dead time, integrating and inverse responses come from, and how to identify and validate a model from data.
pages 1–22
Tank Level Control Studio · pages 23–52
A tank that drains through its own bottom valve is a first-order plant whose gain and time constant both follow the square root of the level, and closing the valve makes it an integrator. What does a step test at one level predict about the loop at another, and what does one proportional loop do on each side?
Two-Tank Level Control Studio · pages 53–83
A splitter valve that sends pump flow past the top tank leaves the bottom level and the process gain where they were, yet turns a second-order plant into a first-order one. What does a step test read at each splitter setting, and what does a tuning or a controller model carried from one lineup to the other do?
TCLab Control Studio · pages 84–111
Two heaters share one small board, and each thermistor lags its heater by more than two minutes. What does a step test reveal about the instrument and the coupling, what do the three velocity forms of PID do differently, and how far does a twin that is its controller's own model speak for the device beside it?
Ball Levitation in a Tube · pages 112–134
A ball that nearly fills a vertical tube floats on air throttled by a servo flap, and because the air is as fast at the top of the tube as at the bottom, its height integrates any error in the valve. What do the momentum balance, a drop test and two step tests say about that integrator, and how does an orifice in series with the valve change what the loop can do?
Flash Steam Level Control Studio · pages 135–159
A rise in steam demand makes the level of a flash vessel rise while the vessel loses water. Which disturbances move the indicated level against the inventory in a heat-recovery unit, and what can single-element, three-element and predictive feedwater control do about it?
Hydroelectric Governor and Penstock · pages 160–180
Opening the gate of a hydro turbine first lowers its power, because the water in the penstock must be accelerated by head taken from the turbine. How far does that right-half-plane zero limit the governor of a unit that supplies a town alone, and what does the same water column demand of the gate when the load is lost?
Electrical Grid Frequency Control · pages 181–203
Grid frequency is the level of the kinetic energy stored in the spinning machines. After a load step, which parameters set how fast it falls, where droop arrests it and how integral action brings it back to 60 Hz?
Spent-Fuel Pool Cooling and Makeup · pages 204–233
The level of a spent-fuel pool is a pure integrator, and its temperature is a self-regulating first-order plant only while a cooling train runs. How does one step test tell which plant the pool is, and what should an operator compute when cooling is lost and the useful number is the time left to a limit?
OPEC Production Quota and the Oil Price · pages 234–257
A cartel that pumps less lifts the oil price within weeks, and the price it then holds pays rivals to drill and consumers to buy efficiency for years. How far can a quota decided at two meetings a year hold the price before the market it protects has gone to the fringe?
TCLab Simulation Studio · pages 258–283
A heater step test can be explained by more than one energy balance. Which terms of a lumped balance can one record identify, and how does a modeler reject a term that lowers the fitting objective but describes a mechanism the data do not contain?
Multivariable Model Identification · pages 284–314
A plant record holds several inputs and outputs that move together, sometimes under feedback. How is the credit for each output divided among correlated inputs, how is an absent path removed exactly, and how is a model judged on data the fit never saw?
Process Monitoring and Diagnostics Studio · pages 315–337
A plant record holds the evidence of a biased flowmeter, a developing fault, a sticking valve and an alarm flood. What does each monitoring statistic actually say about such a record, when one gross error spreads into every balance it enters and the samples of a closed-loop plant are not independent?
pages 338–351